Form CP-MAPSIII-D21, Doc No 303070, Page 36
Insert all three jumpers on the unit at the start of network and the unit at the
end of the network. DO NOT insert the jumpers on the intermediate units.
2.Oncetheashingbegins,releasethepushbutton.Afterthe3redashes,
theLEDcomesongreen.TheLEDthenconrmsrecognitionofthebutton
byashingQUICKLY3timesred-off,andthencomesongreenagain.
3. Wait for about one minute for the factory parameters to be loaded.
The jumpers are used to create built in end-of-line resistance for a BACnet
®
MSTP network.
BACnet
®
MSTP Points List
Option D21 BACnet
®
Point List
Analog Variables
Name Description R/W
BMS
Address
Unit Default Min Max
CC_Temp Cooling Coil Discharge Air Temp R AV1 Deg F
DA_NAClg_SP Discharge Air Temp Neutral Cooling SP R/W AV2 Deg F 70 50 100
DA_NAHtg_SP Discharge Air Temp Neutral Heating SP R/W AV3 Deg F 70 50 140
DA_SP Discharge Air Temp Active SP R AV4 Deg F
DA_SpcClg_SP Discharge Air Temp Space Cooling SP R/W AV5 Deg F 55 50 100
DA_SpcHtCl_SP Discharge Air Temp Space Heat Mode Cooling SP R/W AV6 Deg F 55 50 100
DA_SpcHtg_SP Discharge Air Temp Space Heating Sp R/W AV7 Deg F 90 50 140
DA_Temp Discharge Air Temp R AV8 Deg F
Damper_Cmd Damper Output Command R AV9 % 0 100
DhOADP_SP Dehum OA Dew Point SP R/W AV10 Deg F 58 50 100
Ext_Dmpr_Cmd External Unit Damper Command R AV11 % 0 100
HX1_Mod_Cmd Heating 1 Modulation Command R AV12 % 0 100
HX2_Mod_Cmd Heating 2 Modulation Command R AV13 % 0 100
MA_Temp Mixed Air Temp R AV14 Deg F
OA_Dew_Point Outside Air Dew Point R AV15 Deg F
OA_Hum_BMS
Outside Air Humidity BMS -Sets OA Humidity when OA_Hum_Sel
is set to 1=BMS
R/W AV16 %rH
OA_Hum_Raw Outside Air Humidity R AV17 %rH
OA_Temp_BMS
Outside Air Temp BMS - Sets OA Temp when OA_Temp_Sel is
set to 1=BMS
R/W AV18 Deg F
OA_Temp_Raw Outside Air Temp R AV19 Deg F
OAChgOv_SP OA Change Over SP R/W AV20 Deg F 65 45 80
RH_Mod_Out Reheat Modulation Output % R AV21 % 0 100
SF_VFD_Cmd Supply Fan VFD Command R AV22 % 0 100
SpcEffClgSP Space Effective Cooling SP R AV23 Deg F
SpcEffHtgSP Space Effective Heating SP R AV24 Deg F
Spc_Temp Space Temp R AV25 Deg F
SpcTempSP Space Temp SP R/W AV26 Deg F 72 65 85
RA_Temp Return Air Temperature R AV27 Deg F
RA_Humidity Return Air Humidity R AV28 % rH
EA_Temp Exhaust Air Temperature R AV29 Deg F
EA_Humidity Exhaust Air Humidity R AV30 % rH
• Jumper P1 adds a 510 ohm polarization resistance between the negative
data line (-) and GND;
• Jumper P2 adds a 120 ohm terminal resistance between the two data
lines (+) and (-);
• Jumper P3 adds a 510 ohm polarization resistance between the positive
data line (+) and the +5 Vdc internal voltage.
8.1 BACnet
®
MSTP
(Cont’d)
R = Read
W = Write
AV = Analog Variable
BV = Binary Variable