Form CP-MAPSIII-D21, Doc No 303070, Page 40
Integer Variables
Name Description R/W Index Name NV Bit# TypeNV Unit Default Min Max
Bldg_Pressure Building Static Pressure R 1 nvoBldg_Pressure SNVT_press_p Pa
Bldg_Press_SP Building Static Pressure SP R/W 2 nviBldg_Press_SP SNVT_press_p Pa 24.9 -124 124
Duct_Press_SP Duct Static Pressure SP R/W 3 nviDuct_Press_SP SNVT_press_p Pa 124 0 622
Spc_Humidity
2
Space Humidity R 4 nvoSpc_Humidity
SNVT_lev_
percent
%rH
SpcHumSP
3
Space Humidity SP R/W 5 nviSpcHumSP
SNVT_lev_
percent
%rH 55 35 75
State_Sel
State Select 2=AUTO 3=COOL 4=HEAT
5=OFF
R/W 6 nviState_Sel SNVT_count 5 2 5
OccMode_Sel
Occ Mode Select 0= Schedule 1= Digital
Input 2= BMS
R 7 nvoOccMode_Sel SNVT_count 1 0 2
Spc_CO2 Space CO2 R 8 nvoSpc_CO2 SNVT_ppm ppm
SpcCO2SP Space CO2 SP R/W 9 nviSpcCO2SP SNVT_ppm ppm 1,000
Duct_Pressure Duct Static Pressure R 10 nvoDuct_Pressure SNVT_press_p Pa
Note 1: Divide the BMS humidity value by 20 before writing to the OA_Hum_BMS variable (scale 1=20%).
Note 2: Multiply the Spc_Humidity value by 10 (scale 1=10%).
Note 3: Divide the desired space humidity set point value by 10 before writing to the SpcHumSP variable (scale 1=10%).
Digital Variables
Name Description R/W Index Name NV Bit# TypeNV Unit Default Min Max
OA_Hum_Sel
Share OA Humidity from BMS (0=Probe
1=BMS)
R/W 18 nviOA_Hum_Sel SNVT_switch Off Off On
OA_Temp_Sel
Share OA Temp from BMS (0=Probe
1=BMS)
R/W 19 nviOA_Temp_Sel SNVT_switch Off Off On
Occupied Occupied Mode Status R 22 nvoOccupied SNVT_switch Off On
Occupied_BMS
Occupied Mode BMS - Sets Unit
Occupancy when OccMode_Sel is set
to 2=BMS
R/W 23 nviOccupied_BMS SNVT_switch Off Off On
Digital
Variables
Digital Outputs
Name Description R/W Index Name NV Bit# TypeNV Unit Default Min Max
Alm_Rly_Cmd Unit General Alarm Relay Command R nvoDoStat1 0 SNVT_state Off On
Comp_Stg1_
Cmd
Compressor Stage 1 Command R nvoDoStat1 1 SNVT_state Off On
Comp_Stg2_
Cmd
Compressor Stage 2 Command R nvoDoStat1 2 SNVT_state Off On
Comp_Stg3_
Cmd
Compressor Stage 3 Command R nvoDoStat1 3 SNVT_state Off On
Comp_Stg4_
Cmd
Compressor Stage 4 Command R nvoDoStat1 4 SNVT_state Off On
HX_Stg1_Cmd Heating Stage 1 Command R nvoDoStat1 5 SNVT_state Off On
HX_Stg2_Cmd Heating Stage 2 Command R nvoDoStat1 6 SNVT_state Off On
HX_Stg3_Cmd Heating Stage 3 Command R nvoDoStat1 7 SNVT_state Off On
HX_Stg4_Cmd Heating Stage 4 Command R nvoDoStat1 8 SNVT_state Off On
HX_Stg5_Cmd Heating Stage 5 Command R nvoDoStat1 9 SNVT_state Off On
HX_Stg6_Cmd Heating Stage 6 Command R nvoDoStat1 10 SNVT_state Off On
RH_Cmd Reheat Compressor Command R nvoDoStat1 11 SNVT_state Off On
SF_Cmd Supply Fan Command R nvoDoStat1 12 SNVT_state Off On
LONworks
®
Point List (Cont’d)