7.2.5 Safety components
The safety components should be replaced at the end of their life
cycle indicated in the following table.
Tab. L
ATTENTION
The specified life cycles do not refer to the
warranty terms indicated in the delivery or
payment conditions.
Safety component Life cycle
Flame control
10 years or 250.000
operation cycles
Flame sensor
10 years or 250.000
operation cycles
Gas valves (solenoid)
10 years or 250.000
operation cycles
Pressure switches
10 years or 250.000
operation cycles
Pressure adjuster 15 years
Servomotor (electronic
cam)(if any)
10 years or 250.000
operation cycles
Oil valve (solenoid)(if any)
10 years or 250.000
operation cycles
Oil regulator (if present)
10 years or 250.000
operation cycles
Oil pipes/ couplings
(metallic) (if present)
10 years
Fan impeller 10 years or 500.000 start-ups