Riello MULTI SENTRY MST 100 - User Manual

Riello MULTI SENTRY MST 100
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...

Table of Contents

Questions and Answers

  • S
    Samantha JohnsonAug 27, 2025
    What does code S07 mean on my Riello MULTI SENTRY MST 100?
    • E
      Evan GoldenAug 27, 2025
      If your Riello UPS displays code S07, it indicates that the batteries are flat and the UPS is waiting for the battery voltage to exceed the set threshold. You can either wait for the batteries to recharge or manually force power-on via the “ON” menu.
  • D
    duncanbethanyAug 27, 2025
    What does it mean when my Riello UPS shows codes A39, A40 and the replace batteries LED is on?
    • L
      Lynn Frazier DDSAug 27, 2025
      If your Riello UPS displays codes A39 or A40 and the red "Replace Batteries" LED is on, it means the batteries haven't passed their periodic efficiency test. It's recommended to replace the batteries, as they may no longer provide sufficient autonomy. Battery replacement must be performed by qualified personnel.
  • M
    maureenramosAug 25, 2025
    What to do if there is no load voltage arriving from my Riello UPS?
    • O
      orodriguezAug 26, 2025
      If there is no load voltage from your Riello UPS, consider these possibilities: 1. Check that the load is properly connected to the output terminals. 2. Ensure that the switch behind the door (SWOUT) is closed. 3. Verify that the UPS is not in standby mode. If it is, perform the startup sequence. 4. Confirm that the Stand-by OFF mode is not selected, as this mode only powers loads during blackouts. 5. If the UPS has malfunctioned and the automatic bypass isn't working, insert the manual bypass (SWMB) and contact the nearest service center.
  • D
    daniel78Aug 23, 2025
    What to do if Riello MULTI SENTRY MST 100 does not go into standby mode with mains power?
    • D
      Donna HerringAug 25, 2025
      If your Riello UPS doesn't enter standby mode despite mains power, check the following: * Ensure the mains are correctly connected to the input terminals as per the installation instructions. * Verify the neutral connection is present, as the UPS requires it to operate. Failure to connect the neutral can damage the UPS or the load. * Confirm the switch behind the door (SWIN) is closed. * Check for a blackout; verify the presence of mains voltage. If there is no mains voltage, switch on via batteries to power the load. * Check for upstream protection intervention and reset the protection, ensuring there is no output overload or short to the UPS.

Summary

UPS Connection Details

UPS Installation Procedures

Electrical Connections and Cabling

Connection Cable Section Sizing

Table detailing required cable cross-sections for input, output, and battery.

Preliminary Connection Operations

Safety checks and preparatory steps before electrical connections.

Hookup Instructions

Detailed steps for making the electrical connections.

Electrical System Connection Diagrams

Protection Devices and Safety

Short-Circuit Protection Mechanisms

How the UPS limits current during short circuits.

Input Line Thermal Magnetic Switches

Recommendations for upstream AC protection switches.

Battery Line Fuses and Protection

Requirements for external battery line surge protectors and fuses.

Differential Protection

Guidelines for differential switches in various system configurations.

Output Line Protection

Recommended fuses and thermal switches for output selectivity.

Optional Auxiliary Sockets

Remote Maintenance Bypass Installation

Using the UPS

First Start-Up and Settings

Procedure for initial power-on and basic configuration.

Operating Modes and Manual Bypass

Explanation of different modes and safe use of manual bypass.

UPS Configuration Options

Communication Ports and Interfaces

UPS Software Management

Monitoring and Control Software

Using PowerShield³ for UPS management and event notification.

Configuration Software Usage

Accessing and modifying UPS parameters via special software.

Troubleshooting Common Issues

UPS Status, Alarm, and Error Codes

Technical Data and Specifications

Riello MULTI SENTRY MST 100 Specifications

General IconGeneral
Power Rating100 kVA
Power (W)90 kW
Frequency50/60 Hz
TechnologyIGBT
EfficiencyUp to 96%
Form FactorTower
Input Voltage400 V
Output Voltage400 V
TopologyOnline double conversion
Battery TypeVRLA
Communication InterfaceRS232, USB
Operating Temperature0°C to 40°C
Battery Backup TimeVaries based on battery configuration