EasyManua.ls Logo

Riello RL 50 - Hoses; Opening the burner; Closing the burner

Riello RL 50
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6423
30
GB
Maintenance
SIGNAL FAULT POSSIBLE CAUSE SOLUTION
No blink The burner does
not start
1 - No electrical power supply . . . . . . . . . . . . . Close all switches - Check fuses
2 - A limit or safety control device is open. . . . Adjust or replace
3 - Control box lock-out . . . . . . . . . . . . . . . . . . Reset control box (no sooner than 10 s
after the lockout)
4 - Pump is jammed . . . . . . . . . . . . . . . . . . . . Replace
5 - Erroneous electrical connections . . . . . . . . Check connections
6 - Defective control box . . . . . . . . . . . . . . . . . Replace
7 - Defective electrical motor. . . . . . . . . . . . . . Replace
2 pulses

After pre-purge and
the safety time, the
burner goes to
lockout at the end
of the safety time
8 - No fuel in tank; water on tank bottom. . . . . Top up fuel level or suck up water
9 - Inappropriate head and air damper adjust-
ments
Adjust, see page 17 and page 23
10 - Fuel solenoid valves fail to open (1st stage
or safety)
Check connections; replace coil
11 - 1st nozzle clogged, dirty, or deformed . . . . Replace
12 - Dirty or poorly adjusted firing electrodes . . Adjust or clean
13 - Grounded electrode due to broken insula-
tion
Replace
14 - High voltage cable defective or grounded . Replace
15 - High voltage cable deformed by high tem-
perature
Replace and protect
16 - Ignition transformer defective. . . . . . . . . . . Replace
17 - Erroneous valves or transformer electrical
connections
Check
18 - Control box defective . . . . . . . . . . . . . . . . . Replace
19 - Pump unprimed . . . . . . . . . . . . . . . . . . . . . Prime pump and see “Pump unprimes”
20 - Pump/motor coupling broken . . . . . . . . . . . Replace
21 - Pump suction line connected to return line Correct connection
22 - Valves up-line from pump closed . . . . . . . . Open
23 - Filters dirty: line - pump - nozzle . . . . . . . . Clean
24 - Defective photocell or control box . . . . . . . Replace photocell or control box
25 - Photocell dirty. . . . . . . . . . . . . . . . . . . . . . . Clean
26 - 1st stage operation of cylinder is faulty . . . Change the cylinder
27 - Motor protection tripped . . . . . . . . . . . . . . . Reset thermal relay
28 - Defective motor command remote control
device
Substitute it
29 - Missing phase thermal cut-out trips . . . . . . Reset thermal cut-out when third phase
is re-connected
30 - Incorrect motor rotation direction . . . . . . . . Change motor electrical connections
4 pulses

The burner starts
and then goes into
lockout
31 - Photocell short-circuit. . . . . . . . . . . . . . . . . Replace photocell
32 - Light is entering or flame is simulated . . . . Eliminate light or replace control box
7 pulses

Flame detachment 33 - Poorly adjusted head . . . . . . . . . . . . . . . . . Adjust, see page 17,
34 - Poorly adjusted or dirty firing electrodes . . Adjust, see Fig. 12 on page 17
35 - Poorly adjusted fan air gate: too much air . Adjust
36 - 1st nozzle is too big (pulsation) . . . . . . . . . Reduce 1st nozzle delivery
37 - 1st nozzle is too small (flame detachment) Increase 1st nozzle delivery
38 - 1st nozzle dirty, or deformed . . . . . . . . . . . Replace
39 - Inappropriate pump pressure Adjust to between 10 and 14 bar
40 - 1st stage nozzle unsuited to burner or boiler See Nozzle Table, page 16; reduce 1st
stage nozzle
41 - Defective 1st stage nozzle . . . . . . . . . . . . . Replace
The burner does
not pass to 2nd
stage
42 - Control device TR does not close . . . . . . . Adjust or replace
43 - Defective control box . . . . . . . . . . . . . . . . . Replace
44 - 2nd stage sol. valve coil defective . . . . . . . Replace
45 - Piston jammed in valve unit . . . . . . . . . . . . Replace entire unit

Table of Contents

Related product manuals