Technical description of the burner
4.8 Firing rates
The burners RLS 28- 38 - 50 can work in two ways: one-stage or
two-stage.
The MAXIMUM OUTPUT is chosen within area A.
The MINIMUM OUTPUT must not be lower than the minimum
limit of the diagram:
RS 28 = 81 kW
RS 38 = 105 kW
RS 50 = 115 KW
The firing rate value (Fig. 2) has been obtained
considering an ambient temperature of 20 °C, an
atmospheric pressure of 1013 mbar (approx. 0 m
a.s.l.), and with the combustion head adjusted as
shown on page 18.
Pressure in the chamber
pressure - mbar
Thermal power -
kW
Fig. 2
RS 28
D3612
Pressure in the chamber
pressure - mbar
Thermal power -
kW
RS 38
Pressure in the chamber
pressure - mbar
Thermal power -
kW
RS 50