EasyManua.ls Logo

Riello RTC-80 Series - Suitable Fuels; Burners

Riello RTC-80 Series
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
GENERAL
APPROVED CARBON MONOXIDE DETECTORS: Each carbon monoxide
detector as required in accordance with the above provisions shall
comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certied.
SIGNAGE: A metal or plastic identication plate shall be perma-
nently mounted to the exterior of the building at a minimum
height of eight (8) feet above grade directly in line with the ex-
haust vent terminal for the horizontally vented gas fueled heating
appliance or equipment.
The sign shall read, in print size no less than one-half (1/2) inch in
size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
INSPECTION: The state or local gas inspector of the side wall hor-
izontally vented gas fueled equipment shall not approve the in-
stallation unless, upon inspections, the inspector observes carbon
monoxide detectors and signage installed in accordance with the
provisions of 248 CRM 5.08(2)(a) 1 through 4.
b) EXEMPTIONS: The following equipment is exempt from 248 CRM
5.08(2)(a) 1 through 4:
The equipment listed in Section 10 entitled “Equipment Not
Required To Be Vented” in the most current edition of NFPA
54 as adopted by the board;
Product Approved side wall horizontally vented gas fueled
equipment installed in a room or structure separate from
the dwelling, building or structure used in whole or in part
for residential purposes.
c) MANUFACTURERS REQUIREMENTS - GAS EQUIPMENT VENTING SYS-
TEM REQUIRED: When the manufacturer of Product Approved side
wall horizontally mounted gas equipment provides a venting sys-
tem design or venting system components with the equipment,
the instructions provided by the manufacturer for the installation
of the equipment and venting shall include:
Detailed instructions for the installation of the venting sys-
tem or the venting system components;
A complete parts list for the venting system design or vent-
ing system.
d) MANUFACTURERS REQUIREMENTS - GAS EQUIPMENT VENTING SYS-
TEM NOT PROVIDED: When the manufacturer of Product Approved
side wall horizontally vented gas fueled equipment does not pro-
vide the parts for the venting of ue gases, but identies “special
venting systems”, the following requirements shall be satised by
the manufacturer:
The referenced “special venting systems” shall be included
with the appliance or equipment installation instructions;
The “special venting systems” shall be Product Approved by
the Board and the instructions for that system shall include
a parts list and detailed installation instructions.
e) A copy of all instructions for all Product Approved side wall hor-
izontally vented gas fueled equipment, all venting instructions, all
parts lists for venting instructions and/or venting design instruc-
tions shall remain with the appliance or equipment at the com-
pletion of the installation.
1.10 Suitable fuels
Permissible fuels
Natural gas from the public gas supply in accordance with
national regulations with a total sulphur content < 15ppm.
LP in accordance with national regulations with a content
of elementary sulphur < 1.5 ppm and volatile sulphur < 50
ppm.
Ultra Low Sulphur Diesel in accordance with national regu-
lations with a content of elementary sulphur < 15 ppm (for
use as back-up fuel in condensing operation).
Heating oil type 2 when boiler return temperature is not
lower than 140 °F; non-condensing operation. See the
warranty statement for additional details.
A variety of alternate fuels such as biodiesel, jet fuel A, etc
may also be utilized. Contact
R for applicability.
9
Do not use gasoline, crankcase drainings, or any oil contain-
ing gasoline.
The boiler must only be operated with the specied fuels.
Only burners that are suitable for the specied fuels may
be used.
Observe the manufacturer's burner selection list and the
burner manufacturer's instructions.
1.11 Burners
Follow the burner manufacturer’s instructions when tting the
burner. A pre-drilled burner plate is included with the boiler.
An adapter plate may be required if a non-standard burner is
used (see table).
As standard, the burner plate gasket must be trimmed in order to
t the burner blast tube.
The installer must cut the hole 3/8" larger than the blast tube di-
ameter.
The combustion chamber door must be opened to allow the
burner to be mounted.
If the burner head is too long to open/close the combustion
chamber door, the burner will have to be removed prior to the
opening/closing of the door.
For reduction of burner capacity according to altitude make refer-
ence to the burner manual.
9
After the burner is installed, ll the gap between the burner
tube and the refractory material in the door with the ceramic
insulation supplied loose with the boiler.
RTC 1000-
80
RTC 1300-
80
RTC 1700-
80
RTC 2300-
80
Fireside
pressure
drop
inch W.C. 1.284 1.846 2.007 2.208
mbar 3.2 4.6 5.0 5.5
RTC 3000-
80
RTC 3800-
80
RTC 4700-
80
RTC 5500-
80
Fireside
pressure
drop
inch W.C. 2.288 2.529 2.729 2.970
mbar 5.7 6.3 6.8 7.4
At maximum output with water temps supply/return of 176/140 °F
(80/60 °C), CO2=9.7% and O2=3.6%.

Table of Contents

Related product manuals