-11-
(6) Control-output selection etc. ( )
Set-value (SV) display unit
VALUE DESCRIPTION
Direct action (Type D) Direct / reverse action
Reverse action (Type F, A, W) selection
PID action (Type D, F) 1 Control action
Heating / cooling PID action (Type A, W) 1 type selection
Time proportional output (M, V, G output) 2 Control output type
Continuous output (Current 4 to 20 mA DC) selection (Heating side)
Time proportional output (M, V output) 2 Control output type
Continuous output (Current 4 to 20 mA DC) selection (Cooling side)
1 Type D : PID action [Direct action]
Type F : PID action [Reverse action]
Type A : Heating / cooling PID action [Air-cooling]
Type W : Heating / cooling PID action [Water-cooling]
2 M output : Relay contact G output : Trigger (For triac driving)
V output : Voltage pulse
Cautions
1. Conduct setting so as to meet the instrument specification. An incorrect setting may cause a malfunction.
2. When control action is of the type D or F, “Control output type selection (Cooling side)” setting is ignored.
3. For the REX-C100, always set the control action type selection to PID action.
4. ” setting displays are only “ ”and “ ”.