Filter Change
Reminder
This feature will flash FILT in the
display after the elapsed run time
to remind the user to change the
filter. A setting of OFF will disable
this feature.
Next step
Prev step
You can adjust the filter change
reminder from OFF to 2000
hours of runtime in 50 hour
increments. Tap the second
button from the top left side of
the thermostat to display the
current filter elapsed runtime.
OFF
Room
Temperature
Calibration
This feature allows the installer to
change the calibration of the room
temperature display. For example,
if the thermostat reads 70° and
you would like it to read 72° then
select +2.
Next step
Prev step
You can adjust the room
temperature display to read
3° above or below the factory
calibrated reading.
0
Minimum
Compressor
On Time
This feature allows the installer to
select the minimum run time for the
compressor. For example: A setting
of 4 will force the compressor to run
for at least 4 minutes every time the
compressor turns on, regardless of
the room temperature.
Next step
Prev step
You can select the minimum
compressor run time from OFF,
3, 4, or 5 minutes. If 3, 4, or 5
is selected, the compressor will
run for at least the selected time
before turning off.
OFF
Tech Settings LCD Will Show Adjustment Options Default
TECHNICIAN SETUP MENU
12