EasyManuals Logo

Robin LG072 User Manual

Robin LG072
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #54 background imageLoading...
Page #54 background image
11.
TROUBLE-SHOOTING
Set generator to normal rpm.
(Cause)
(Remedy)
YES
Voltmeter defectiv
1
NO
Fuse checked? Fuse burnt out. Fuse burnt out
(or
No
Fuse Breaker)
Wire checked?
leads unconnected.
Wrong wiring
Exciting coil
defective
Primary exciting circuit
in
AVR defective
Resistance outside
Slip ring defective
TOK
Brush defective
(Check winding resistance.)
Field coil short
range of
6
-
13n or broken
Main coil broken
resistance in 9-1.)
(See the description
of
winding
resistance in
9-1
.)
OK
Check AVR. AVR broken
Replace.
Replace.
Wire correctly.
Replace exciting coil.
0
Replace AVR.
Clean, replace.
Check, replace.
Replace.
Replace stator.
Replace stator.
Replace AVR.
-
52
-