NOTES: Wiring between generator and electrical appliances
1. Allowable current of cable
Use a cable with an allowable current that is higher than the rated input current of the load
(electrical appliance). If the input current is higher than the allowable current of the cable used, the
cable wilt become excessively heated and deteriorate the insulation, possibly burning it out.
Table 7-2 shows cables and their allowable currents for your reference.
2. Cable length
If a long cable is used, a voltage drop occurs due to the increased resistance in the conductors
decreasing the input voltage to the load (electrical product). As a result, the load can be damaged.
Table 7-2 shows voltage drops per 100 meters of cable.
I
Nominal cross
sectlon
i Resistance Current Amp.
I
I
mm2 No. A No. / mm Q/iOOm 1A 3A j 5A 8A ] lOA 12A 15A!
0.75 18
i
7 i 30/0.18 2.477 2.5Vi8V 12.5V - --I-
I
:
1.27 16 12 ! 50:0.18 i 1.486
;
1.5v 5v 7.5V 12V 15V 18V -
!
I
2.0 14 : 17 37 i 0.26 0.952 lV 3v I ; 1 5v j 8V ; 1OV 12V 15V i
3.5 12-10
I
! 23 45!0.32 j 0.517
I
: - j 1.5V 1 2.5V ] 4V 5V j 6.5V 7.5V
I ! 1 ’ 5.5 10-8 25 70:0.32 : ’ ’ 0.332 / - ( 1V (
2V ! 2.5VI 3.5Vi 4V 1 5V i
Table 7-2
Voltage drop indicates as V =
-&XRXIXe
R mens resistance (
0 /lo0 m) on the above table.
I means electric current through the wire (A).
g means the length of the wire (m).
The length of wire indicates round length,it means twice the length from generator to electrical tools.
- 42 -