Ethernet Network Appliance (with Network Address Translation) 13
Publication
9300-IN001A-EN-P - December 2012
5. Insert the exposed part of the positive wire into the connection
labeled DC+ and the exposed part of the return wire into the
connection labeled DC-.
Make sure that you cannot see any wire lead. Only wire with insulation
should extend from the connector.
6. Use a ratcheting-torque screwdriver to torque the power and relay
connector captive screws (above the installed wire leads) to 0.23 N•m
(2.0 lb in.).
7. Connect the other end of the positive wire (the one connected to
DC+) to the positive terminal on the DC power source, and connect
the other end of the return wire (the one connected to DC-) to the
return terminal on the DC power source.