22 Rockwell Automation Publication 5069-UM007A-EN-P - February 2019
Chapter 2 Compact 5000 EtherNet/IP Adapter Power Requirements
SA Power - Additional Notes
Remember the following:
We recommend that you use a separate power supply for the SA power
connection from the power supply that is used with the MOD power
connection.
The actual current in a Compact 5000 I/O system SA power bus current
draw changes based on the operating conditions at a given time.
For example, the SA power bus current draw on some modules is
different if all channels power field devices or half of the channels power
field devices.
Not all Compact 5000 I/O modules use SA power.
For example, the 5069-ARM, 5069-OB16, 5069-OB16F, 5069-OW4I,
and 5069-OX4I modules do not use SA power.
Some Compact 5000 I/O modules use field-side power but do not draw
it from a SA power bus. The modules receive field-side power from an
external power supply that is connected to the module RTB.
For example, the 5069-OB16 and 5069-OB16F modules use Local
Actuator (LA) terminals, that is, LA+ and LA- terminals for all
module channels.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley 5069-AENTR and is the answer not in the manual?

Rockwell Automation Allen-Bradley 5069-AENTR Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley 5069-AENTR
CategoryAdapter
LanguageEnglish

Related product manuals