Using Quick Start
5-9
MOTOR
RATED
ARM
AMPS
(P.008)
The rated armature
current from the
motor nameplate.
Parameter Range:
0 to 3000.0 amps
Default Setting:
8.0 amps
Parameter Type:
Configurable
!
ATTENTION:
This parameter must be less than the motor rated armature
amps or drive current rating listed on the motor nameplate. If this is
configured incorrectly, overcurrent or excess heating of the motor could
result. Failure to observe this precaution could result in damage to, or
destruction of, the equipment.
MOTOR
RATED
ARM
VOLTS
(P.009)
The rated armature
voltage as it is listed
on the motor
nameplate.
Parameter Range:
160 to 675 volts
Default Setting:
240 volts
Parameter Type:
Configurable
REVERSE
DISABLE
(P.015)
Applies only to
regenerative drives. If
you have a
non-regenerative
drive, Quick Start
automatically skips
this parameter.
Parameter Range:
OFF
ON
Default Setting:
*
OFF
Parameter Type:
Configurable
When
ON
,
REVERSE
DISABLE
does not allow the speed reference to drop below zero.
When
OFF
, the speed reference can drop below zero and the drive can operate in
the reverse direction.
REVERSE
DISABLE
is forced to
ON
when:
•
The drive has a non-regenerative (S6) power unit.
•
FEEDBACK
SELECT
is set to
AC
TACH
.
•
FEEDBACK
SELECT
is set to
PULSE
TACH
and
PULSE
TACH
QUADRATURE
(P.208) is set
to
OFF
.