PROBLEM ALARM POSSIBLE CAUSE ACTION
The gate does not
open or close.
(QH
(EnE5)
Encoder malfunction. Press TEST button. Replace the encoder if the pro-
blem persists.
.SXZKܪHNJSYUT\JWXZUUQ^ If the unit contains dirt, moisture, insects or other
foreign matter, disconnect from mains power and
clean the board and the encoder. Replace the enco-
der if the problem persists.
Batteries functioning 9MJGFYYJWNJXFWJFQRTXYܫFY
(Q(
Encoder calculation error. Repeat acquisition procedure.
Inverter thermal overload circuit
breaker tripped.
Function is restored automatically within 2 min.
EW/2
(btLO)
Flat batteries. Wait for mains power to be restored.
VWR3
ܫFXMNSL
Release device open.
Close the release handle and turn the key to the
close position. Check that the release contact is
connected correctly.
Acquisition procedure
does not complete
correctly.
QR 3+
Motor calibration failed. Repeat acquisition procedure.
If the problem persists, check the cable connecting
the encoder to the motor.
Check if release handle is open.
Check that the motor turns without impediment.
Contact technical support in case of any problems.
Problems with the encoder circuit
or on the connecting cable.
Check the good condition of the onnection cable.
Disconnect and then reconnect from main power.
Give a command (opening/step-by-step, ... ).
If QR3+ does NOT appear, repeat the learning procedure.
If QR3+ appears again contact the technical assistance.
$3 3(
TEST button pressed accidentally.
Repeat acquisition procedure.
Safety devices in alarm state. Press the TEST button and check the safety
device/s in alarm state and the connections of the
safety devices.
Excessive voltage drop. Repeat acquisition procedure.
Check mains voltage.
Incorrect setting of parameters
 and .
Adjust parameters  and  correctly for the
weight and speed of the gate leaf.
DS S/
Travel length error. Move gate into completely closed position (FC li-
mit switch signal must be active) and repeat the
procedure.
Check cable of limit switches. Replace the cable if
the problem persists.
Reset default controller unit parameters and repeat
the procedure.
Stroke length less than the minimum allowed: in-
crease the length.
DSS
Maximum permitted travel length
exceeded
Reduce the ride. Contact technical assistance (tra-
vel exceeding the maximum allowed by the techni-
cal characteristics).
Remote control has
limited range and does
not work while auto-
mated gate is moving.
The radio transmission is im-
peded by metal structures and
reinforced concrete walls.
Install the antenna outside.
Flat batteries. Replace the transmitter batteries.
9MJܫFXMNSLQNLMYNX
not working.
'ZQG1*)GQT\STWܫFXMNSLQNLMY
wires disconnected.
Check LED circuit and/or connector wires.
Gate open indicator
lamp does not work.
Bulb blown or wires
disconnected.
Check the bulb and/or wires.
Gate does not perform
desired manoeuvre.
Incorrect setting of parameter . Select the correct installation position with para-
meter .
E RG
Incorrect selection of the battery type.
Change the value of the parameter .
N.B.: Press the TEST button to temporarily cancel the alarm.