[51][FW] – Setting output function for OUT1 output
The [FW] specifies the output function assigned to the programmed output line. The OUT1 refers to the internal
relay output of the controller. For [FW] codes refer to section Outputs in this manual.
Default: <FW=99>, Door Lock
[52][FW] – Setting output function for OUT2 output
The OUT2 refers to the internal transistor output of the controller. Programming rules as for the OUT1.
Default: <FW=99>, Door Lock
[53][FW] – Setting output function for OUT3
The OUT2 refers to the internal transistor output of the controller. Programming rules as for the OUT1.
Default: <FW=07>, Prealarm+Door Ajar+Forced Entry
[54][FW] – Setting output function for OUT4
The OUT4 refers to the REL1 output located on the XM-2 extension module. Programming rules as for the
OUT1.
Default: <FW=99>, Door Lock
[55][FW] – Setting output function for OUT5 (REL2 output on XM-2 extension module)
The OUT5 refers to the REL2 output located on the XM-2 extension module. Programming rules as for the
OUT1.
Default: <FW=99>, Door Lock
[57][F] – Setting option: Timed lock-out
Program [X]=0 to disable option or [X]=1 to enable option.
Default: <F=0>,
[59][F] – Setting option: Deactivate door release when door open
Program [F]=0 to enable option or [F]=1 to disable option.
Default: <F=0>,
[61][New MASTER card] – Programming new MASTER card
The old MASTER card is deleted and replaced buy new one.
[62][New MASTER PIN][#] – Programming new MASTER PIN
The old MASTER PIN is deleted and replaced buy new one.
[63][New INSTALLER card] – Programming new INSTALLER card
The old INSTALLER card is deleted and replaced buy new one.
[64][New INSTALLER PIN][#] – Programming new INSTALLER PIN
The old INSATLLER PIN is deleted and replaced buy new one.
[66][NF][F] – Setting authorization for user commands
The [NF] specifies the user command. Program [F]=0 if you want the particular user commands without
MASTER identifier or program [F]=1 if you want to enable MASTER authorization request.
Default: All User Commands require MASTER authorization
Examples:
[66][17][0] – The MASTER identifier is not required for user command no. 17
[66][17][1] – The MASTER identifier is required for user command no. 17
[66][*][0] – Clear authorization request for all user commands
Clears request for MASTER identifier for all user commands.
[66][*][1] – Set authorization request for all user commands
Sets request for MASTER identifier for all user commands.
[67][WCD][D] – Setting option: Facility Code
The [WCD] specifies the Facility Code for cards, the [WCD] must be from range from 000 to 255.
The [D] specifies if the cards with the Facility Code will have an AWA Privilege or not. Program [D]=1 to assign
AWA Privilege to all cards with Facility Code or program [D]=0 if you want Facility cards without AWA Privilege.
Default: Option is not active, no Facility Code defined
[67][*] – Clear option: Facility Code
Disables the Facility Code option.
[71][SS] – Setting the AUX1 timer in seconds (SS=00-99) or
[71][*][MM] – Setting the AUX1 timer in minutes (MM=01-99)
The timer value can be defined in seconds (command [71][SS]) or in minutes (command [71][*][MM]).