Loading...
Reference Manual
00809-0100-4708, Rev AA
June 2010
Rosemount 708
B-2
Hazardous Locations
Certificates
North American Certifications
Factory Mutual (FM) Approvals
I5 FM Intrinsic Safety
Intrinsically Safe for Class I, Division 1, Groups A, B, C, D
Zone Marking: Class I, Zone 0, AEx ia llC
Temperature Codes T4 (T
amb
= -50 to 70° C)
Ambient temperature limits: -50 to 85° C
Intrinsically Safe when installed in accordance with Rosemount drawing
XXXXX-XXXX.
For use with Rosemount Power Module P/N XXX-XXXX-XXXX only.
Enclosure Type 4X / IP65
Warning: Does not meet the surface resistivity requirements, and it
must only be cleaned with a damp cloth to avoid electrostatic
charging.
CSA - Canadian Standards Association
I6 CSA Intrinsic Safety
Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D.
Temp Code T3C
Enclosure Type 4X / IP65
For use with Rosemount Power Module P/N XXX-XXXX-XXXX only
Intrinsically Safe when installed per Rosemount drawing XXXXX-XXXX
Warning: Does not meet the surface resistivity requirements, and it
must only be cleaned with a damp cloth to avoid electrostatic
charging.
European Certifications
I1 ATEX Intrinsic Safety
Certificate No.: BASEEFA07ATEXXXXXX II 1G
Ex ia IIC T4 (T
a
= -60 °C to 70 °C)
IP65
For use with Rosemount Power Module P/N XXX-XXXX-XXXX only
1180
Does not meet the surface resistivity requirements, and it must only be
cleaned with a damp cloth to avoid electrostatic charging.