Controller Functionality
AYC-Qx4 family manual Page 40
d. Enable Bypass Code and enable the
door chime.
Enter a code not ending with 0.
4) System returns to its normal mode.
You will hear three
beeps.
The Door LED will turn off.
The Mode LED will turn green.
Setting Fail Safe/Secure Operation, Tamper Siren and Lock
Strike Release Time
1) Enter Programming mode.
2) Press “6” to enter Menu 6
The Mode LED will flash
green.
3) Construct a code using instructions hereafter.
First Digit
For fail secure operation, the first digit is set to 0.
For failsafe operation, the first digit is set to 1.
Second Digit
Siren Time in minutes (1-9, 0-disabled)
Third and Fourth Digits
Enter the number of seconds (from 1 to 99) that
you want the Lock Strike to be released.
For example, 0312 means Fail Secure Operation, a 3-minute Siren,
and a 12-second Lock Strike release time.
? ? ? 0
6
? ? ? ?
Mode/Transmit
Door/Program
Green
Mode/Transmit
Door/Program
Green
Mode/Transmit Door/Program
Green
Green