LOKA HAHB remote control
EN
74
Installation and user manual
Rotation & Back-up indication
When there are two units, press the button to select the rotating function, and press
“CONFIRM”to turn on or o the rotating function.
1. Press “CONFIRM” to set the rotating time,then press the button „ ” or „ ”, to set
time. Setting time Range :1~99h,the default time is 10 hours.
2. Step 2 set high temperature co-open temperature -- or 26~32 degrees -- that is,
this function is invalid. When the ambient temperature is 26~32 degrees, when
the ambient temperature is greater than or equal to the set temperature, the two
machines will run 24 degrees at the same time in the COOL mode.
3. Step 3 set the low-temperature co-open temperature -- or 5-15 degrees -- that is, this
function is invalid. When the ambient temperature is 5-15 degrees, when the ambient
temperature is lower than the set temperature, the two machines will run at the same
time for 24 degrees to make the heating mode.
4. Step 4: set which machine will run rst. Select A or B.
5. After this function is turned on, as long as the air conditioner is running at the setting
hour, it will automatically turn on another air conditioner and turn o the current air
conditioner. Press the POWER button to switch to another one immediately. A or B
icons icker to indicate the corresponding air conditioning failure.
Automatically switch to another machine when running time is reached or machine
failure occurs.