This sub-parameter value is used to monitor the higher limit pressure. Set the threshold in a
range from "0.0" to "10.0" bar.
Threshold Limit 3
This parameter is used to set the pressure threshold 3. The device triggers a fault message
if the current inlet pressure overshoots threshold 3.
Off
This parameter value does not trigger any message or alarm.
Custom
This sub-parameter value is used to monitor the higher limit pressure. Set the threshold in a
range from "0.0" to "10.0" bar.
Load for Opening
Applicable for Posidapt Super and Ultra
This parameter is used to determine minimum pressure required to open the valve from full
close position.
The actual value (auto calibration) is displayed in the “Load for Opening” in Values and
Counters under Counter Thresholds and Trends.
Threshold Limit 1
This parameter is used to set threshold 1 for the deviation in Load for Opening of current
value from the reference value.
Off
This parameter value does not trigger any message or alarm.
Custom
This parameter is used to set the threshold 1 in bar.
The device triggers a fault message if the difference between the current value and the
reference value exceeds threshold 1. The value can be set from 0.0 to 10.0 bars.