7.26 Remote Motor Control (RMC)
The RMC OPC90 block is used to retrieve and control the exception reported
output from Bailey Remote Motor Control blocks (function code 136).
Restrictions: This OPC90 block can be utilized with all Bailey interface types
except serial port module (SPM & CPM02).
TAGNAME TYPE ACCESS DESCRIPTION
ADDR_RING VT_I2 Config/Read Bailey ring address.
ADDR_NODE VT_I2 Config/Read Bailey node address.
ADDR_MODULE VT_I2 Config/Read Bailey module address.
ADDR_BLOCK VT_I2 Config/Read Bailey block address.
F1LSD0 VT_BSTR Config/Read Feedback 1 state zero logic state descriptor.
F1LSD1 VT_BSTR Config/Read Feedback 1 state one logic state descriptor.
F2LSD0 VT_BSTR Config/Read Feedback 2 state zero logic state descriptor.
F2LSD1 VT_BSTR Config/Read Feedback 2 state one logic state descriptor.
PERM1LSD0 VT_BSTR Config/Read Permissive 1 state zero logic state descriptor.
PERM1LSD1 VT_BSTR Config/Read Permissive 1 state one logic state descriptor.
PERM2LSD0 VT_BSTR Config/Read Permissive 2 state zero logic state descriptor.
PERM2LSD1 VT_BSTR Config/Read Permissive 2 state one logic state descriptor.
OUTLSD0 VT_BSTR Config/Read Output state zero logic state descriptor.
OUTLSD1 VT_BSTR Config/Read Output state one logic state descriptor.
MESSAGE VT_BSTR Read Provides the block operational message.
TAG VT_BSTR Read Provides the block name.
TAGLONG VT_BSTR Read Provides the block long OPC path name.
TAGDESC VT_BSTR Read Provides the block descriptor.
FACE_TYPE VT_I2 Read Faceplate type (value of RMC block S14).
QUALITY VT_BOOL Read Current quality of Bailey values (0-good, 1-
bad).
DISC_ACT VT_BOOL Read Alarm active indicator.
OUT VT_BOOL Read/Write The Bailey discrete output value.
OUT_TEXT VT_BSTR Read/Write Bailey RCM discrete output value as a string
(see note 1).
RED_CMD VT_BSTR Read/Write Red tag command (see red tag users section).
RED_TAG VT_BOOL Read Red tag indicator (0 – no, 1 – yes).
RED_USERS VT_BSTR Read Red tag users (current user names or codes).
F1 VT_BOOL Read State of feedback number 1.
F1_TEXT VT_BSTR Read State of feedback number 1 as a string.
F2 VT_BOOL Read State of feedback number 2.
F2_TEXT VT_BSTR Read State of feedback number 2 as a string.
FAULT VT_BOOL Read Fault has occurred indicator.
ERR_CODE VT_I2 Read Fault error code (see note 2).
FAULT_ACK VT_BOOL Read/Write Fault acknowledgment (see note 3).
PERM1 VT_BOOL Read Permissive #1 indicator.
PERM1_TEXT VT_BSTR Read Permissive #1 indicator as a string.
PERM2 VT_BOOL Read Permissive #2 indicator.
PERM2_TEXT VT_BSTR Read Permissive #2 indicator as a string.
BAD_START VT_BOOL Read Bad start indicator.
HOLD_STATUS VT_BOOL Read Status on hold indicator.