OPC90 Server
7.12 Harmon O O)
9 to retrie
ny t nction c
lid for Bailey interface types INICI03,
TAG
y Analog utput (HA
The HAO OPC 0 block is used ve the exception reported output from
Bailey Harmo Analog Ou put (fu ode 223) blocks.
Restrictions: This OPC block is only va
INICI12 and INICI13.
NAME TYPE ACCESS DESCRIPTION
ADDR_RING VT_I2 Config/Read Bailey ring address.
ADDR_NODE VT_I2 Config/Read Bailey node address.
ADDR_MODULE VT_I2 Config/Read Bailey module address.
ADDR_BLOCK VT_I2 Config/Read Bailey block address.
MESSAGE VT_BSTR Read Provides the block operational message.
TAG VT_BSTR Read Provides the block name.
TAGLONG VT_BSTR Read Provides the block long OPC path name.
TAG Provides the block descriptor. DESC VT_BSTR Read
CHAN_NAME VT_BSTR Read Channel name assigned to this point
CHAN_TYPE VT_I2 Read Channel type code
CH
Overdrive)
AN_STATE VT_BOOL Read Channel state (0-Ok, 1-Open, 2-Short, 3-
ALARM_CODE VT_I2 Read Alarm code
QUALITY VT_BOOL Read Current quality of Bailey values (0-good, 1-bad).
QUAL_PROP VT_BOOL Read Propogated Quality (0-Good, 1-Bad)
OUT VT_R4 Read Current output value from Bailey.
HIGH VT_R4 Read High signal value in Engineering Units.
LOW VT_R4 Read Low signal value in Engineering Units.
SIG_CHANGE VT_R4 Read Significant change in % of range
EU VT_I2 Read Engineering Units Code.
EU_TEXT VT_BSTR Read Engineering Units String.
HI_LIM VT_R4 Read/Write The setting for the alarm limit used to detect the
high alarm condition. Writing a new value to
this attribute automatically tunes the alarm limit
of the associated Bailey block.
LO_LIM VT_R4 Read/Write The setting for the alarm limit used to detect the
low alarm condition. Writing a new value to this
attribute automatically tunes the alarm limit of
the associated Bailey block.
HI_ACT VT_BOOL Read High alarm active indicator.
LO_ACT VT_BOOL Read Low alarm active indicator.
OVR_ENABLE VT_BOOL Read Override allowed (0-No, 1-Yes)
OVR_VALUE VT_R4 Read Override value
OVR_STATUS VT_BOOL Read Value overridden (0-No, 1-Yes)
STAT_INHIBT VT_BOOL Read Status inhibit (0-No, 1-Yes)
SUSPECT VT_BOOL Read Value suspect (0-No, 1-Yes)
DRIVEN_LO VT_BOOL Read Low overdriven value (0-No, 1-Yes)
DRIVEN_HI VT_BOOL Read High overdriven value (0-No, 1-Yes)
CONFIG_ERR VT_BOOL Read Configuration error exists (0-No, 1-Yes)
READBACK VT_BOOL Read Readback status (0-Good, 1-Bad)
REFERENCE VT_BOOL Read Reference status (0-Good, 1-Bad)
CALIBRATION VT_BOOL Read Calibration status (0-Good, 1-Bad)
SIM_ENABLE VT_BOOL Read Simulation enable indicator
SIM_BLOCK VT_I2 Read Simulation value block number
The RoviSys Company Version 7.0 Page 78