EasyManua.ls Logo

RTA 460 - Page 15

RTA 460
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Default IP Address – 192.168.0.100
460 Gateway User Manual Page 10
Figure 2-5 Enable Modbus RTU Master configuration
3. Click on the Enabled? checkbox.
The Module’s Detail options expand when enabled. See Figure 2-6.
Figure 2-6 Modbus RTU Master configuration details
4. Select the appropriate communication options from the drop-down menus.
Note: Only one RS232, RS485, or CAN port setting can be active per unit. For example, a
unit cannot have two ports set for RS232 or two ports set for CAN. If the same mode
is selected for two communication modules, a message similar to Figure 2-7 displays.
Figure 2-7 Serial port incompatibility error
5. Click on
Save.
The selections stay visible on the Communication Module Configuration screen, although
they are grayed out (until you select again). See Figure 2-8.
Edit

Related product manuals