EasyManua.ls Logo

RTA 460 - Page 17

RTA 460
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Default IP Address – 192.168.0.100
460 Gateway User Manual Page 12
8. For each new Device Buffer that should be enabled (1-32), click on the Add Remote
Modbus RTU Slave
button.
9. Click
Edit in the Action column. See Figure 2-10.
Figure 2-10 Modbus RTU Master registers and program tags
10. Enter the Save Address and select the data types (RegType) from the drop-down menus
for the registers. Enter the address and length for each data type in this Device Buffer.
11. Select
Save. The Master and Client Module External Device List re-displays with the
information entered for that Device Buffer. See Figure 2-11. To add another Device
Buffer, click on the Add Remote Modbus RTU Slave button and then edit that buffer’s
settings.

Related product manuals