Default IP Address – 192.168.0.100
460 Gateway User Manual Page 46
2. Click on next to next to Serial Module 1 (or Serial Module 2).
The Enabled? prompt displays. See Figure 2-60.
Figure 2-60 Enable Serial Module configuration
3. Click on the Enabled? checkbox.
The Module’s Detail options expand when enabled. See Figure 2-61.
4. Select the appropriate communication options.
Data flow is controlled in three ways: maximum message length, receive character
timeout, and delimiters. You can use any combination (or none) of these methods.
For Your Information: The Device Status and Summary button on the 460
Gateway’s Main Web page displays the data messages transmitted and the
method that terminated that message, which aides in troubleshooting.
Edit