MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
35
3.4. Parameter settlement
Service timeT1
Water treatment capacity
Q=V
R
×K÷Y
D
m
3
Hardness of Inlet Water (mmol/L)
Exchange factor (mmol/L) 400
1000. Down-flow regeneration, take
400 750. Up-flow regeneration,
take 4501000. If the inlet water
hardness is higher, the factor is
smaller.
Resin volume( m
3)
By hours: T1=Q÷Q
h
Hour
Water treatment capacity per hour (m
3
/h)
Water treatment capacitym
3
By daysT1=Q÷Q
d
Day
Water treatment capacity per day (m
3
/d)
Water treatment capacity (m
3
)
Backwash time T2
It is subject to the turbidity of inlet water. Generally, It is suggested
to be set 10 15 minutes. The higher the turbidity is, the longer
backwash time can be set. However, if the turbidity is more than 5FTU, it
should be better to install a filter in front of the exchanger.
Brine& slow rinse time T3
T3=(4050)×H
R
min.
Generally, T3=45H
R
min.
In this formula, H
R
——The height of resin in exchange tank (m.)
Brine refill timeT4