MODEL: N74A1-63510/N74A3-63610/N74B1-63510B/N74B3-63610B
5
1.3. Service Condition
Runxin Valve should be used under the below conditions:
Requirement
Working
conditions
Water pressure
0.2 MPa0.6 MPa
Water
temperature
5℃~50
Working
environment
Environment
temperature
5℃~50
Relative
humidity
≤95%25
Electrical facility
AC100240V/5060Hz
Inlet water
quality
Water turbidity
5FTU
Water hardness
First Grade Na
+
6.5mmol/L
Second Grade Na
+
10mmol/L
Free chlorine
0.1mg/L
Iron
2+
0.3mg/L
CODMn
2mg/L(O
2
)
In the above table, First Grade Na+ represents First Grade Na+
Exchanger. Second Grade Na+ represents Second Grade Na+ Exchanger.
When the water turbidity exceeds the conditions, a filter should be
installed on the inlet of control valve.
When the water hardness exceeds the conditions, the outlet water
hardness will hardly reach the requirement of boiler feed water0.03
mmol/L. It is suggested to adopt second grade softener.