Page #21 background image
MODEL 53515/53615/63515/63615/73515/73615
17
Hardness, Regeneration Factor, the
controller will calculate the System
Capacity. Regeneration mode same as
A-01.
A-04
Intelligent Meter Immediate: Meter
Immediately Regeneration Type, but by
setting Resin Volume, Feed Water
Hardness, Regeneration Factor, the
controller will calculate the System
Capacity. Regeneration mode same as
A-02.
Service
Days
1-03D
099 Days
Only for Time Clock Type, regeneration
by days
Regenerati
on Time
02:00
02:00
00:0023:59
Regeneration time: “:” lights on
Resin
Volume
500
500
202000
Resin volume in brine tank (L)
Feed
Water
Hardness
Yd1.2
1.2
0.19.9
Feed water hardness (mmol/L)
Exchange
Factor
AL.65
0.65
0.300.99
Relate to the raw water hardness. When
hardness is higher, the factor is smaller.
Water
Treatment
Capacity
200
09999 9
Water treatment capacity in one circle
(m
3
)
Interval
Backwash
Times
F-00
00
00~20
Only suited for 73515/73615
Rinsing
Frequenc
y
F-00
00
00~20
Only suited for 53515/53615
Backwash
Time
1000
09959
Backwash time (Minute : Second)
Brine Draw
Time
6000
09959
Brine draw time (Minute : Second)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Runxin F99A3 and is the answer not in the manual?

Runxin F99A3 Specifications

General IconGeneral
BrandRunxin
ModelF99A3
CategoryControl Unit
LanguageEnglish

Related product manuals