MODEL 53515/53615/63515/63615/73515/73615
39
Maxim
um
Interval
Regen
eration
Days
1. In maximum interval regeneration days display status,
it shows H-30. Press and enter into program set
mode. and 30 flash
2. Press or to adjust the interval regeneration
days
3. Press to finish adjustment, press to turn
back.
Signal
Output
Mode
1. In signal output mode display status, it shows b-01.
Press and enter into program set mode. and 01
flash
2. Press or to adjust the mode
3. Press to finish adjustment, press to turn
back.
For examplethe fast rinse time of a softener is 12 minutes. After
regenerating, the chloridion in the outlet water is always higher than
normal, indicating that the time is not enough for fast rinse. If you want
the time to set to 15 minutes, the modification steps as follows:
Press and hold both and to lift the button lock status
lights off;
Press and lights on;
Press or continuously until lights on. Then the
digital area shows: 5-12:00
Press , and12 flash;
Press continuously until 12 changed to 15;
Press , there is a sound “Di” and the figure stop flashing; the
program back to enquiry status;
If you want to adjust other parameters, you can repeat the
steps from to . If you don’t, press and quit from the enquiry
status, the display will show the current service status.