- 61 -
F0.09
Running direction selection Factory Setting 0
Setting Options
0 Forward
1 Reverse
2 Reverse running prohibited
The turning direction of the motor can be changed through setting options of this
functional code. It is equivalent to adjusting any two lines (U, V, W) of the motor for
changing the turning direction.
Note: The turning direction of electric motor will return to its original state after
initialization of parameters. Please use this very cautiously under the occasion that
the system has finished debugging procedures and any change of the turning
direction of electric motor is prohibited.
F0.10
Max. output frequency Factory Setting 50.00Hz
Setting Options
10.00~600.00Hz
F0.11
Upper limit frequency source selection Factory Setting 0
Options
0 Keypad setting (F0.12)
1
AVI terminal (100% corresponds to the setting
frequency of F0.12)
2 Reserved
3
Multi-step speed terminals (Multi-step speed frequency
setting is the upper limit frequency)
4 Communications interface
Define the source of the upper limit frequency. The upper limit frequency can come
from keypad settings (F0.12), or from analog inputs. When using an analog input to
set the upper limit frequency, the value of 100% of the analog input is corresponding
to F0.12.