8000m Series
- 60 -
1 or 3), the two parameters are used to determine the adjustable range of the
auxiliary frequency source. F0.05 can determine the corresponding range reference
for the auxiliary frequency source, if the corresponding object is the maximum
frequency(F0.10), the range of the auxiliary frequency source will be fixed; if the
corresponding object is the master frequency source X, the range of the auxiliary
frequency source will change along with the change of master frequency source X.
F0.07
Frequency reference selection Factory Setting 0
Setting
Options
0 Mater frequency source X
1 Auxiliary frequency source Y
2 Mater frequency source X plus auxiliary frequency source Y
3
Max. value of (mater frequency source X, auxiliary frequency
source Y)
0: Present frequency reference is master frequency source X
1: Present frequency reference is auxiliary frequency source Y
2: Present frequency reference is master frequency source X plus auxiliary
frequency source Y
3: Select the bigger one of the value of master frequency source X and auxiliary
frequency source Y as the frequency reference
F0.08
Keypad setting frequency Factory Setting 50.00 Hz
Setting Options
0.00Hz F0.10 (the setting value is valid when the master or
auxiliary frequency source is digital setting)
When the master frequency source is selected as “digital setting UP/DN key”, the
value of this functional code is the original value of the frequency settings of the
VFD.