6 Description of the nameplate
EB 3132-2 EN 11
Description of the nameplate
Control loop
oscillates
Valve too large for control task Recalculate the K
VS
coefficient and contact
SAMSON.
Time constant too large for con
-
trol loop
Fill the thermowell with conductive paste, remove
the thermowell and use a sensor with a smaller
time constant.
Fig. 5 · Nameplate
1 Model number
2 Modification index
3 Date of manufacture
4 Type designation
Entries in the other spaces:
K
VS
or C
V
coefficient
Upper differential pressure in bar or psi
Flow rate set point in m³/h
Max. permissible temperature in °C or °F
Max. permissible differential pressure
D
p
Nominal pressure as PN or ANSI Class
1 2
4
3