4.6 Status modification
The classification of the status alarms can be
changed as required. The following assign
-
ment of the states are:
4
Maintenance alarm
4
Maintenance required/Maintenance
demanded
4
No message possible
Select
Positioner
folder (>
Error control
>
Status classification
) to modify the classifica
-
tion of standard alarms issued by EXPERT.
Select
Positioner
folder (>
Error control
>
Status classification > Extended)
to modify
the classification of alarms issued by
EXPERT+.
Note!
All additional alarms generated by EXPERT
+
have the status “No message” by default.
On resetting the positioner parameters to
their default settings (Code 36), the status
classification is also reset to the default set
-
ting.
If modifications that have already been
made should be kept, we recommend
uploading them on a PC before performing
a reset and then downloading them onto the
positioner again afterwards.
Note!
In the Type 3730-5 Positioner (Foundation
Fieldbus), block error alarms as well as the
condensed states can be assigned to events .
Refer to EB 8384-5 EN for further
instructions.
30 EB 8388 EN
Status and diagnostic alarms