If the same status classification is to be used
in future, you can upload the settings onto a
PC over, for example, the TROVIS-VIEW
software.
Mounting the positioner onto another con
-
trol valve
As the EXPERT
+
extended diagnostics pro
-
vides statements about the entire control
valve, the data from statistical information
AUTO and tests MAN need to be reset
when the positioner is attached to a different
control valve.
After mounting the positioner on the new
control valve, perform a reset over Code 36
and re-initialize the positioner. This leads to
the most of the diagnostic functions being
reset.
We recommend additionally to manually re-
set the long-term travel histogram and the
long-term cycle counter histogram as well as
the logging by selecting the
Diagnosis
folder
(>
Reset
).
EB 8388 EN 33
Resetting diagnostic parameters