102 EB 8389 EN
Leakage sensor
7.1.2.3 Monitoring
If the determined mean sound level exceeds
the 'Alarm limit 2', the positioner generates
a 'Inner leakage' message with status classi-
cation selected for 'Alarm limit 2 exceed-
ed'.
If the determined mean sound level exceeds
the 'Alarm limit 3', the positioner generates
a 'Inner leakage' message with status classi-
cation selected for 'Alarm limit 3 exceed-
ed'.
Diagnosis > Status messages > Extended
Inner (seat) leakage
7.1.2.4 Resetting single status
messages
The repetition test (diagnostic parameters,
measured data and analysis) and the 'Inner
leakage' message can be reset by selecting
and executing the command "Reset 'leakage
detection - repetition test'".
If the test is restarted and a repetition test
has already been performed, the analysis of
this repetition test is overwritten.
Operation > Reset
Reset 'Leakage detection – repetition test'