EB 8389 EN 109
Appendix
9 Appendix
9.1 Code list
Code
No.
Parameter – Readings/
values [default setting]
Description
Codes with marked with an asterisk (*) must be enabled with Code3 prior to conguration.
48* d0 Current temperature
–55.0 to 125.0
Current operating temperature [°C] inside the positioner
(accuracy ±3%)
Read only
d1 Minimum temperature
[20]
The lowest temperature [°C] below 20°C that has ever occurred.
Read only
d2 Maximum temperature
[20]
The highest temperature [°C] above 20°C that has ever occurred.
Read only
d3 Num-
ber of zero calibrations
Indicates number of zero calibrations performed since the last initial-
ization
Read only
d4 No. of initializations The total number of initializations that have been performed since
the last reset
Read only
d5 Zero limit
0.0 to 100.0% of the
nominal range, [5.0%]
Limit for zero monitoring
Used for error monitoring of the zero shift.
d6 Condensed state Condensed state, made up from the individual states.
OK OK
C Maintenance required
CR Maintenance demanded
B Maintenance alarm
I Function check (Types3730-4/-5)
S Out of specication (Types3730-2/-3)
Read only
d7 Start reference test
[No], YES, ESC
Triggering of a reference test for the functions: Drive signal y steady-
state (d1) and drive signal y hysteresis (d2)
The reference test can only be activated in manual mode as the valve
moves through its entire travel range.