EasyManua.ls Logo

Samson 3730-3 - Trend of Travel End Position

Samson 3730-3
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EB 8389 EN 59
Statistical information
4.8 Trend of travel end position
3730-2 3730-3 3731-3 3730-4 3730-5 3731-5
The travel end position trend is used to detect
an alternating zero point or a creeping zero
point shift due to seat and plug wear or dirt
between the seat and plug.
Data are recorded in the background re-
gardless of the operating mode selected if
the tight-closing function (Code 14) is active.
Data logging does not need to be activated.
The course of end position records the valve
position x and the drive signal y together
with the time stamp by the operating hours
counter when the valve moves to the lower
end position. The new recorded valve posi-
tion is compared to the last saved zero point.
If it differs by the 'Recording threshold' from
the last value, the data of the new zero point
are saved.
A graph of the recorded valve positions at
the lower end position is plotted over the
number of measurements.
The positioner saves the valve positions in a
circular buffer, which holds 30 measured
values at one time. The recorded measured
data are listed in the 'Lower end position'
folder.
Fig.8: Diagnosis > Statistical information > Trend of travel end position