114 EB 8389 EN
Appendix
Code
No.
Parameter – Readings/
values [default setting]
Description
Codes with marked with an asterisk (*) must be enabled with Code3 prior to conguration.
F5 Max. test duration
exceeded
The test was not completed within the max. test time and was auto-
matically canceled.
F6 Test canceled manually The test has been manually canceled by the user.
49* F7 Measured data
memory full
Max. memory capacity for measured data reached. After recording
100 measured values per variable, logging is stopped, but the test
continues until it is completed.
F8 Int. solenoid valve The test was canceled by the activation of the solenoid valve.
F9 Supply pressure/
friction
The test was canceled due to insufcient supply pressure or excessive
friction.
h Application type (valve)
h0 Application type
[No], YES, ESC
Not Type3730-4
No Control valve
YES Open/close (on/off) valve
Depending on the adjusted application type, the positioner responds
differently in automatic mode and there are differences in the diag-
nostic functions.
h1 Operating point
0.0 to [100.0%] of the
valve position
Types3730-2/-3, Type 3731-3 only
The valve is moved to this valve position as soon as the reference
variable exceeds the limit operating point (Code 49 – h5).
h2 Limit fail-safe position
0.0 to 20.0% of the
reference variable,
[12.5%]
Types3730-2/-3, Type 3731-3 only
The valve is moved to its fail-safe position (SAFE) when the value
falls below this limit.
h3 Lower limit to start test
[25.0% of reference
variable]
Types3730-2/-3, Type 3731-3 only
The valve remains in its last valid position between the fail-safe posi-
tion limit and the bottom test limit. A partial stroke test is performed
after six seconds when the valve is between the top and bottom test
limit.
Read only
h4 Upper limit to start test
[50.0% of reference
variable]
Types3730-2/-3, Type 3731-3 only
The valve remains in its last valid position between the top test limit
and the operating point limit.
Read only