34 EB 8389 EN
Statistical information
This function is only active when 'Trigger
band' ≠ 0.
'Trigger edge' = "Band entry"
Top band limit =
Trigger value + ½
trigger band
Bottom band limit =
Trigger value ½
trigger band
Trigger value
Trigger band
w, x, y, e
The conditions for starting a trigger event
are met when the value exceeds the lower
limit ('Trigger value' – ½ 'Trigger band') or
falls below the upper limit ('Trigger value' +
½ 'Trigger band').
This function is only active when 'Trigger
band' ≠ 0.
The bottom band limit assumes the value
0.0% or 0.0
1
/
s
at the lowest. The top band
limit assumes the value 100.0% or 100.0
1
/
s
at the most.
1.
Diagnosis > Statistical information > Data
logger
Selection: Trigger
2. Trigger status: Start trigger via set point,
valve position, drive signal or set point
deviation
Trigger value:
0.0 to 100.0 %, [99.0 %] (set point, valve
position, set point deviation)
0.0 to 10000.0
1
/
s
, [99.0
1
/
s
] (drive signal)
Trigger band:
0.0 to 100.0%, [99.0%] (set point, valve
position, set point deviation)
0.0 to 10000.0
1
/
s
, [99.0
1
/
s
] (drive signal)
Pre-trigger time:
0.0s to 100 x 'Scan rate', [0.0s]
Trigger edge: [Low signal/falling edge/
bottom band exit], High signal/rising edge/
top band exit, Band exit, Band entry
1)
3. Scan rate: 0.2 to 3600.0 s, [1.0 s]
4. Start data logger
1)
Types3730-4/-5: [Bottom band exit], Top
band exit, Band exit, Band entry
4.2.2.3 Triggered by internal sole-
noid valve/forced venting
3730-2 3730-3 3731-3 3730-4 3730-5 3731-5
1)
1)
Function available in rmware 1.5x and lower
Triggering by the internal solenoid valve/
forced venting is only active when an inter-
nal solenoid valve/forced venting is installed
in the positioner. See 'Internal solenoid
valve/forced venting' reading (Code 45).
The measured values are included in the trig-
gered data logging when the solenoid valve
is triggered or the forced venting is activat-
ed.
1.
Diagnostics > Data logger
Selection: Trigger