3. Start initialization by right-clicking
Initialization
and selecting
Execute
.
How long the initialization procedure lasts
depends on the actuator transit time and may
take a few minutes.
Operational test
1. Start the test mode by clicking icon.
If the positioner is not connected (online), TROVIS-VIEW establishes the connection auto-
matically.
A warning appears that the operating mode will be changed into the manual mode
(MAN).
2. Confirm the warning message.
The Modify Final Value window appears.
3. Enter required final value.
4. Confirm the final value by clicking the
Write
button.
The final value is download onto the positioner and the valve is positioned using this new
value.
The positioner exits the manual mode (MAN) and changes back to the operating mode
originally selected.