16.6 Status classification
Alarms are classified in the positioner with a status when an error occurs. States include
“Maintenance alarm“, “Maintenance required“, “Maintenance demanded “, “Function
check“ and “No message“.
4
Maintenance alarm
The positioner cannot perform its control task due to a functional fault in the device or in
one of its peripherals or an initialization has not yet been successfully completed.
4
Maintenance required
The positioner still performs its control task (with restrictions). A maintenance demand or
above average wear has been determined. The wear tolerance will soon be exhausted or
is reducing at a faster rate than expected. Maintenance is necessary in the medium term.
4
Maintenance demanded
The positioner still performs its control task (with restrictions). A maintenance demand or
above average wear has been determined. The wear tolerance will soon be exhausted or
is reducing at a faster rate than expected. Maintenance is necessary in the short term.
4
Function check
Test or calibration procedures are being performed. The positioner is temporarily unable
to perform its control task until this procedure is completed.
4
No message
When this classification is active, it does not have any affect on the condensed state.
You can change the status classification in the
Positioner
folder (>
Error control
>
Classifica-
tion report
).
88 EB 8384-5 EN
Settings in TROVIS-VIEW software
Status classification of a single alarm TROVIS-VIEW3/DD
Maintenance alarm red
Maintenance required/demanded blue
Function check orange
No message white