24 EB 8546 EN
Troubleshooting
7 Troubleshooting
Risk of injury due to high pressure.
Shut off the air line before performing work
on the supply pressure regulator.
Leakage between supply pressure regulator
andadapterplate:
Î Check whether the diverting gasket
(Fig.3 and Fig.4) is installed and the
two fastening screws are tightened prop-
erly.
Excessiveblow-offovertheventingbore:
Î Check whether the diverting gasket
(Fig.3 and Fig.4) is installed correctly.
Air capacity drops and the output pressure
drops:
Î Check the lter cartridge for dirt and
make sure the set point is correctly ad-
justed.
Pressure drop
Î Unscrew the lter receptacle and renew
the lter cartridge (order no. 8504-
9027).
WARNING
!