6 EB 8546 EN
Design and principle of operation
2 Design and principle of oper-
ation
The supply pressure regulator is used to sup-
ply pneumatic measuring and control equip-
ment with a constant air supply. The maxi-
mum 12bar pressure of the compressed air
network in a plant is reduced to an adjust-
able minimum pressure of 0.2 to 1.6bar or
0.5 to 6bar.
At the inlet side, the supply pressure regula-
tor is equipped with a lter cartridge with a
mesh size of 20μm. In addition, the regula-
tor can also be equipped with a lter recep-
tacle and a pressure gauge on the outlet side.
20
Fig.1: Overview of Type4708
The compressed air at the inlet ows across
the lter through the free cross-section be-
tween the seat (1.1) and plug (1.2) and
leaves the output with a reduced pressure
depending on the plug position.
The output pressure to be controlled is trans-
mitted to the diaphragm (2.1) over the con-
necting bore (1.3) and converted into a posi-
tioning force. This force is used to move the
valve plug depending on the force of the po-
sitioning spring (6).
Turning the set point screw (7) causes the
spring force to change and, as a result, the
required set point is adjusted.
The set point ranges of the supply pressure
regulator from 0.2 to 1.6bar and 0.5 to
6bar are determined by various tensions of
the installed positioning spring (6).
Condensed water contained in the com-
pressed air can be collected and drained
when the lter cartridge (11) is mounted hor-
izontally or the lter receptacle (13) is sus-
pended downwards. The screw plug (12)
can be unscrewed or the manual drainage
(16) can be activated to drain condensed