EB 8546 EN 9
Design and principle of operation
2.2 Technical data
Supply pressure regulator Type4708-xx
Values measured with ¼” connection
Supply pressure 1.6 to 12bar
(24 to 180psi)
Set point range 0.2 to 1.6bar (3 to 24psi) or 0.5 to 6bar (8 to 90psi)
Air consumption at 7bar
supply pressure
≤0.05m
n
³/h
Dependency on inlet pressure < 0.01bar/Δp = 1bar
Reversing error 0.1 to 0.4bar
(depending on set point)
Hysteresis < 0.1bar
Filter cartridge mesh size 20µm · Optionally 5µm
Compliance
Pressure gauge
Indicating range 0 to 1.6bar (0 to 24psi) or 0 to 6bar (0 to 90psi)
Connection G
1
/
8
Ambient temperature ranges
Type4708 -10 -11 -12 -13 -14 -17 -53 -54 -55 -62 -64 -82 -83 -84 -86 -87
Standard –25 to +70°C
1)
• • • • • •
–25 to +80°C • • • • • • • • • •
Low-tem-
perature
version
–40 to +80°C •
–50 to +70°C
1)
• • • • • •
–50 to +80°C • • • • • • • • •
1)
Applies also to rotating supplementary lter
Weights
Type4708 -10 -11 -12 -13 -14 -17 -53 -54 -55 -62 -64 -82 -83 -84 -86 -87
kg
(approx.)
0.48 0.58 0.66 1.65 1.2 1.0 0.68 0.95 0.37 0.4 0.5 0.4 0.24 0.32 0.59 0.95