Setting indoor unit addresses and installation option
64
English
Installation manual
05 series installation option (Detailed)
Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation
PAGE MODE
Use of Auto Change
Over for HR only in Auto
mode / Use of Cooling
only indoor unit of HR
(When setting SEG3)
Standard heating
temp. Offset
(When setting SEG3)
Standard cooling temp.
Offset
(When setting SEG3)
Standard for mode
Cooling
Indication
and
Details
Indication Details
Indication Details Indication Details Indication Details Indication Details Indication Details
0 5
0
Follow
product
option
0 0 °C 0 0 °C 0 1 °C
1 0.5 °C 1 0.5 °C 1 1.5 °C
1
Use Auto
Change
Over for HR
only
2 1 °C 2 1 °C 2 2 °C
3 1.5 °C 3 1.5 °C 3 2.5 °C
4 2 °C 4 2 °C 4 3 °C
2
Use Cooling
only indoor
unit for HR
5 2.5 °C 5 2.5 °C 5 3.5 °C
6 3 °C 6 3 °C 6 4 °C
7 3.5 °C 7 3.5 °C 7 4.5 °C
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation
PAGE
(When setting SEG3)
Standard for mode
Heating
(When setting SEG3)
Time required for mode
change
Compensation option
for Long pipe or height
difference between
indoor units
MTFC (*3) -
Indication
and
Details
Indication Details
Indication Details Indication Details Indication Details Indication Details -
1
0 1 °C 0 5min 0 Default
0
Default -
1 1.5 °C 1 7min
1
(*1) Height
difference
is more
than 30m
or (*2)
Distance
is longer
than 110m
2 2 °C 2 9min
3 2.5 °C 3 11min
4 3 °C 4 13min
2
(*1) Height
difference
is 15~30m
or (*2)
Distance is
50~110m
2 Use -
5 3.5 °C 5 15min
6 4 °C 6 20min
7 4.5 °C 7 30min