10_ preparing the installation
preparing the installation
MOVING THE OUTDOOR UNIT
Select the moving route in advance.
Secure the strength of the carrying to resist against the weight of the outdoor unit while moving.
Do not slant the product more than 30˚(86°F) when carrying it.
(Do not lay the product down sideways.)
The surface of the heat exchanger is sharp. Be careful not to be get injury while moving and installing.
When moving with a crane or straps
Fasten the wire rope as seen in the picture.
To protect damage or scratches, insert a piece of cloth between the outdoor unit and the wire rope.
Fork part
Fork lift
When moving with a fork lift
Insert the fork into the bottom of the outdoor unit carefully.
Be careful that the fork does not damage the outdoor unit.
Wire rope/straps
Plate protection
cloth
Outdoor unit leg
DETACHING FASTENERS
Open the bottom cabinet with screw driver.
The compressors are fastened with nuts in 4 places of only
following models.
RD125VRXF
Detach nut washer, washer and stopper nut from compressors with a tool.
Stopper nutWasherNut washer
Refasten the nut washer only.
Pay your attention not to touch the copper pipes as detaching the fasteners.
The stopper nut and washer should be removed. If this work is not conducted correctly,
the outdoor unit could vibrate and make noise.
Remove
CAUTION
DVM PLUS3 HR_IM_E_32805-2.indd 10 2011-11-11 오후 4:18:11