completing the installation and commissioning _47
ENGLISH
COMPLETING THE INSTALLATION
Measure the power cable terminal (3-phase: R, S, T) and the grounding of the outdoor unit using a
DC 500V ohmmeter before connecting the power.
- The measured value should be over 30
MΩ
.
.
Check the terminal voltage and the phase using a voltmeter and phase test system before connecting
the power.
- R, S, T terminal : 208~230V between wires (R-S, S-T, T-R)
Turn the switch on after checking the terminal.
Check the R410A indoor unit is connected.
If the power cables, R,S and T, are cross wired, E425 error occurs. Check for proper connection
of the power cable.
T
S
R
208~230V
208~230V
208~230V
T
S
R
220V 220V
220V
<ELB>
Never measure the communication terminal to prevent the communication circuit from being
damaged.
Check the short-circuit of the communication terminal using the circuit test system.
CAUTION