30_ installing the unit
installing the unit
WIRING WORK
Manufacturer’s recommended specifications of the circuit breaker
and power cable
1. Basic model
2. Electric Specification
• The relationship between the starting time and the starting current
(Digital Scroll Comp. + Fixed Scroll Comp)
• Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminal is not
below or above listed range limits.
• Maximum allowable voltage variation between phases is 2%(4.6V).
Abbreviations
- MCA: Min. Circuit Amps. (A)
MCA = 1.25 X LOAD1 + LOAD2
( LOAD1: RLA of Fixed Comp. / LOAD2: RLA of Digital Comp. + FLA of Fan Motor)
- RLA: Rated Load Amps. (A)
- OFM: Outdoor Fan Motor
- FLA: Full Load Amps. (A)
- kW : Rated Motor Output (kW)
Capacity(HP) Model MCCB(A) ELB
7.5 RD075VRXFA
50 50A, 30mA, ≤100ms
10 RD100VRXFA
12.5 RD125VRXFA 60 60A, 30mA, ≤100ms
Model
Units
Power
supply
Comp. OFM
Hz Volts Min. Max. MCA RLA kW FLA
RD075VRXFA 60 208-230 187 253 48.1 13.8+21.8 0.63 7
RD100VRXFA 60 208-230 187 253 53.8 19.6+21.8 0.63 7
RD125VRXFA 60 208-230 187 253 61.1 23.4+24.6 0.63 7
Starting current
Starting time
RLA
• Install a circuit breaker. For safety and maintenance, we strongly recommend that
MCCB, ELB and ELCB have to be installed every outdoor unit.
- ELCB : Earth Leakage Circuit Breaker
- MCCB : Molded Case Circuit Breaker
- ELB : Earth Leakage fuse Breaker
• Operate the unit after the refrigerant piping work must be done.
• Do not disassemble or alter the wiring of the unit during the electrical wiring work.
If not, the unit may be damaged.
CAUTION