30_ installing the unit
installing the unit
WIRING WORK
Manufacturer’s recommended specifications of the circuit breaker
and power cable
1. Basic model
2. Electric Specification
The relationship between the starting time and the starting current
(Digital Scroll Comp. + Fixed Scroll Comp)
Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminal is not
below or above listed range limits.
Maximum allowable voltage variation between phases is 2%(4.6V).
Abbreviations
- MCA: Min. Circuit Amps. (A)
MCA = 1.25 X LOAD1 + LOAD2
( LOAD1: RLA of Fixed Comp. / LOAD2: RLA of Digital Comp. + FLA of Fan Motor)
- RLA: Rated Load Amps. (A)
- OFM: Outdoor Fan Motor
- FLA: Full Load Amps. (A)
- kW : Rated Motor Output (kW)
Capacity(HP) Model MCCB(A) ELB
7.5 RD075VRXFA
50 50A, 30mA, 100ms
10 RD100VRXFA
12.5 RD125VRXFA 60 60A, 30mA, 100ms
Model
Units
Power
supply
Comp. OFM
Hz Volts Min. Max. MCA RLA kW FLA
RD075VRXFA 60 208-230 187 253 48.1 13.8+21.8 0.63 7
RD100VRXFA 60 208-230 187 253 53.8 19.6+21.8 0.63 7
RD125VRXFA 60 208-230 187 253 61.1 23.4+24.6 0.63 7
Starting current
Starting time
RLA
Install a circuit breaker. For safety and maintenance, we strongly recommend that
MCCB, ELB and ELCB have to be installed every outdoor unit.
- ELCB : Earth Leakage Circuit Breaker
- MCCB : Molded Case Circuit Breaker
- ELB : Earth Leakage fuse Breaker
Operate the unit after the refrigerant piping work must be done.
Do not disassemble or alter the wiring of the unit during the electrical wiring work.
If not, the unit may be damaged.
CAUTION
DVM PLUS3 HR_IM_E_32805-2.indd 30 2011-11-11 오후 4:18:26