ENGLISH-46
Field setting mode
Space Heating : Code 40
T
a
#4012
#3034
T
u
T
s
DHW by Booster Heater Only
DHW by Booster Heater Only
Field Setting Value
Main Menu &
Code
Sub Menu Function Description Sub Code Default Min Max Step Unit
Heating Code
40

Heat Pump Heating/DHW Priority

11 0(DHW) 0 1(Heating) - -
Outdoor Temp for Priority

12 0 -15 20 1 ˚C
Heating O

13 35 14 35 1 ˚C
Overshoot

14 2 1 4 1 ˚C
Backup Heater Application

21 0(No) 0 1(Yes) - -
BUH/BSH Priority

22 0(Both) 0 2(BSH) 1 -
Cold weather compensation

23 1(Yes) 0(No) 1 - -
Threshold Temp

24 0 -15 35 1 ˚C
Defrost Backup Temp.

25 15 10 55 5 ˚C
Backup Boiler Application

31 0(No) 0 1(Yes) - -
Boiler Priority

32 0(No) 0 1(Yes) - -
Threshold Temp

33 -15 -20 5 1 ˚C
Mixing valve
Application

41 0(No) 0 1(Yes) - -
Target ΔT(Heating)

42 10 5 15 1 ˚C
Target ΔT(Cooling)

43 10 5 15 1 ˚C
Control factor

44 2 1 5 1 -
Control interval

45 2 1 30 1 min
Running Time

46 9 6 24 3
(x10)
sec
Inverter Pump
Application

51 1(Yes) 0 1(Yes) - -
Target ΔT

52 5 2 8 1 ˚C
Control factor

53 2 1 3 1 -