47
English
Field Setting Mode
Classification Function Detail
Code
(Main
+ sub
menu)
Basic Min. Max. Step Unit
Water Law
Auto heating of wired
remote controller
WL type 2041 1(WL1) 1 2 - -
Use of thermostat - 2091 0(No) 0 2 - -
DHW
Activating hot water
function
DHW application 3011 0(No) 0 1(Yes) - -
Heating mode
Max. 3021 70 45 75 1 °C
Stop 3022 2 0 10 1 °C
Start 3023 5 5 20 1 °C
Minimum Heating
Operation time
3024 5 1 20 1 min.
DHW operation time 3025 30 5 95 5 min.
Heating operation time 3026 3 0.5 10 0.5 hour
Booster heater
Operation 3031 1 (On) 0 (Off) 1 - -
Delayed time 3032 20 20 95 5 min.
Overshoot 3033 0 0 4 1 °C
Disinfection
Operation 3041 1 (Yes) 0 (No) 1 - -
Operation interval 3042 Fri (5)
Sun
(0)
AllDay (7) - day
Start time 3043 23 0 23 1 hour
Target temp. 3044 70 60 75 5 °C
Holding time 3045 10 5 60 5 min
Max. operation time 3046 ߩ 1241hour
Solar heat panel / defrost
signal
Solar heat panel
H/P interlocking /
defrost signal
3061 0 0 3 - -
Heating Heating mode
Heating/hot water
priority
4011
0 (Hot
water)
0
1
(Heating)
--
Heating priority 4012 0 -15 20 1 °C
Heating Off 4013 35 14 35 1 °C
Others Outing mode
Temperature of cooling
water oulet
5011 - - - 1 °C
Room Temperature of
cooling Mode
5012 - - - 1 °C
Temperature of heating
leaving water
5013 25 25 ߩߡ 1°C